Energy measuring equipment and power analysers for energy management and power quality monitoring with real-time diagnosis of electrical energy supply.
Specifications
- Rated voltage L-N, AC277 V
- Rated voltage L-L, AC480 V
- Overvoltage category300 V CAT III
- Auxiliary voltage95 ... 240 V AC; 135 ... 340 V DC
- Three wire (L-N, L-L)Yes
- Four wire (L-N, L-L)Yes
- Quadrants4
- Sampling frequency 50/60 Hz20 kHz
- Measurement points per seconds20 000
- Uninterupted measurementYes
- Measurement results per seconds5
- Harmonics V/A1 st ... 40t h
- Distortion factor THD-U in %Yes
- Distortion factor THD-I in %Yes
- UnbalanceYes
- Positive / negative / zero sequence componentYes
- Transients50 μs
- Short-term iterruptions, eventsYes
- Accuracy V / A0.2 %
- Effective power class0.5 (.../5 A)
- Operating hours counterYes
- Weekly timerYes
- Digital inputs2
- Digital / pulse output2
- Current measurement channel4
- Integrated logicJasic
- Minimum and maximum values for memoryYes
- Memory size for onboard recording128 MB Flash
- Number of memory values5 000 k
- ClockYes
- Error / event recorder functionYes
- SoftwareGridVis-Basic
Accessories